Critical Services

During fire conditions where copper hydrant pipe has been used in un-sprinklered compartments, the heat within the fire compartment can potentially weaken copper pipes making the hydrant system ineffective which compromises the entire fire suppression capacity of the building. To address this, fire hydrant pipes made from copper require fire isolation or critical service protection under AS2419.1 using materials that provide an FRL of no less than -/60/60.

 

Trafalgar has a tested system that meets the AS1530.4 section 12 requirements for critical services with copper hydrant pipes